Parameters ASDA-A3
8-96
Revision December, 2017
8
P3.xxx Communication parameters
P3.000
Address
Address: 0300H
0301H
Default:
0x7F
Control mode: All
Unit:
-
Setting range: 0x01 – 0x7F
Format:
HEX
Data size: 16-bit
Settings:
YX
Z
U
YX
Communication address setting
UZ
Reserved
When using RS-485 to communicate, one servo drive can set only one address. Setting more than one
addresses causes abnormal communications. This address represents the absolute address of the
servo drive in the communication network. It is also applicable to RS-485, CANopen, and DMCNET.
When the communication address of MODBUS is 0xFF, the servo drive automatically receives and and
replies to data regardless of the address, but P3.000 cannot be set to 0xFF.
P3.001
Transmission speed
Address: 0302H
0303H
Default:
0x0203
Control mode: All
Unit:
Bps
Setting range: 0x000 – 0x3405
Format:
HEX
Data size: 16-bit
Settings:
Y
Z
U
X
Transmission speed is divided into U, Z, Y, and X (hexadecimal):
U
Z
Y
X
Communication
port
DMCNET CANopen /
DMCNET
-
RS-485
Range
0 – 3
0 – 4
0
0 – 5
Definition of X value
0: 4800
1: 9600
2: 19200
3: 38400
4: 57600
5: 115200
Definition of Z value
*3
0: 125 Kbit/s
1: 250 Kbit/s
2: 500 Kbit/s
3: 800 Kbit/s
4: 1.0 Mbit/s
-
Summary of Contents for ASD-A3-0121
Page 13: ...Revision December 2017 This page is intentionally left blank...
Page 43: ...Installation ASDA A3 2 20 Revision December 2017 2 This page is intentionally left blank...
Page 105: ...Wiring ASDA A3 3 62 Revision December 2017 3 This page is intentionally left blank...
Page 187: ...Operation Mode ASDA A3 6 36 Revision December 2017 6 This page is intentionally left blank...
Page 467: ...Parameters ASDA A3 8 210 Revision December 2017 8 This page is intentionally left blank...
Page 577: ...Specifications ASDA A3 A 28 Revision December 2017 A This page is intentionally left blank...
Page 597: ...Accessories ASDA A3 B 20 Revision December 2017 B This page is intentionally left blank...
Page 603: ...4 Revision December 2017 This page is intentionally left blank...