Motion Control
ASDA-A3
7-42
Revision December, 2017
7
7.1.5 Trigger methods for the PR command
There are six types of PR triggering methods. They are DI-triggered, Event-triggered,
P5.007-triggered, Capture-triggered (high-speed position capturing), Compare-triggered
(high-speed position comparing), and E-Cam-triggered. You can choose the most suitable
triggering method according to the applications and requirements.
Digital input (DI) triggering
You can choose the PR path to be executed by using the internal registers (Position command
Bit0 – Bit6) and use a command to trigger the selected PR path. Before using DI-triggering
commands, you must define the 8 sets of DI functions, which are [0x11]POS0, [0x12]POS1,
[0x13]POS2, [0x1A]POS3, [0x1B]POS4, [0x1C]POS5, [0x1E]POS6, and [0x08]CTRG (refer to
Table 8.1). You can also set this in the I/O screen of ASDA-Soft, as shown in Figure 7.1.5.1.
Figure 7.1.5.1 I/O screen in ASDA-Soft
Select the PR number to be executed based on the on / off status of DI.POS0–6 and use
DI.CTRG to trigger the specified PR path. See Figure 7.1.5.1 for an example.
Summary of Contents for ASD-A3-0121
Page 13: ...Revision December 2017 This page is intentionally left blank...
Page 43: ...Installation ASDA A3 2 20 Revision December 2017 2 This page is intentionally left blank...
Page 105: ...Wiring ASDA A3 3 62 Revision December 2017 3 This page is intentionally left blank...
Page 187: ...Operation Mode ASDA A3 6 36 Revision December 2017 6 This page is intentionally left blank...
Page 467: ...Parameters ASDA A3 8 210 Revision December 2017 8 This page is intentionally left blank...
Page 577: ...Specifications ASDA A3 A 28 Revision December 2017 A This page is intentionally left blank...
Page 597: ...Accessories ASDA A3 B 20 Revision December 2017 B This page is intentionally left blank...
Page 603: ...4 Revision December 2017 This page is intentionally left blank...