ASDA-A3
Troubleshooting
Revision December, 2017
11-15
11
Checking methods
and corrective
actions
1. Check the values of the communication parameters. Then correctly set
P3.003 and P3.004 or restore the value to default.
2. Check and correctly set the communication address.
3. Check and correctly set the accessing value.
How to clear the
alarm?
DI.ARST
AL020 Serial communication timeout
Trigger condition
and causes
Condition: RS-485 communication error.
Causes:
1. Improper setting of the timeout parameter (P5.003).
2. Servo drive has not received the communication command for a long
time and has timed out (please refer to P5.003).
Checking methods
and corrective
actions
1. Check and make sure the value for the communication timeout
parameter is correct.
2. Check if the communication cable is loose or broken and is correctly
wired.
How to clear the
alarm?
DI.ARST
AL022 RST leak phase
Trigger condition
and causes
Condition: RST power cable is loose or there is no power. The default
setting of AL022 is a warning. To set AL022 as an alarm, you can set
P2.066 [Bit 12].
Cause: RST leak phase.
Checking methods
and corrective
actions
Check if the RST power cable is loose or there is no power. This alarm
occurs when the 1.5 kW (or below) A3 servo drive is not connected to the
three-phase power supply. For 2 kW (or above) A3 servo drives, the alarm
occurs when one single phase is not connected to the power supply.
Correctly connect the power to the servo drive. If the issue persists, please
send your A3 servo drive back to the distributor or contact Delta.
How to clear the
alarm?
DI.ARST
AL023 Early overload warning
Trigger condition
and causes
Early overload warning
Checking methods
and corrective
actions
1. Check if your servo drive is overloaded and refer to the corrective
actions for AL006 for troubleshooting.
2. Check if the value of P1.056 is set too low. If yes, please increase the
value, which should be over 100 to disable the warning function.
Summary of Contents for ASD-A3-0121
Page 13: ...Revision December 2017 This page is intentionally left blank...
Page 43: ...Installation ASDA A3 2 20 Revision December 2017 2 This page is intentionally left blank...
Page 105: ...Wiring ASDA A3 3 62 Revision December 2017 3 This page is intentionally left blank...
Page 187: ...Operation Mode ASDA A3 6 36 Revision December 2017 6 This page is intentionally left blank...
Page 467: ...Parameters ASDA A3 8 210 Revision December 2017 8 This page is intentionally left blank...
Page 577: ...Specifications ASDA A3 A 28 Revision December 2017 A This page is intentionally left blank...
Page 597: ...Accessories ASDA A3 B 20 Revision December 2017 B This page is intentionally left blank...
Page 603: ...4 Revision December 2017 This page is intentionally left blank...