Field Setting
SiBE811001EB
125
CONVENI-PACK
3. Outdoor fan relation
[2-5] Low noise setting by the outdoor air temperature
The outdoor fan revolution can be changed according to the outdoor temperature.
<Operation mode: 5-35, 64, 65, 70, 74, 75, 80>
Tax1, Tay1, Tax2, and Tay2 can be set in setting Page 2-21.
Ambient temperature
Fan tap
H1P
H2P
H3P
H4P
H5P
H6P
H7P
Factory
setting
Ambient temp.
≤
Tax1
8
k
h
h
h
h
h
k
Tay1< Ambient temp.
≤
Tax2
9
Ambient temp. > Tay2
11
Set 1
Ambient temp.
≤
Tax1
9
k
h
h
h
h
k
h
Tay1< Ambient temp.
≤
Tax2
10
Ambient temp. > Tay2
11
Set 2
Ambient temp.
≤
Tax1
7
k
h
h
h
k
h
h
Tay1< Ambient temp.
≤
Tax2
8
Ambient temp. > Tay2
11
Set 3
Ambient temp.
≤
Tax1
11
k
h
h
k
h
h
h
Tay1< Ambient temp.
≤
Tax2
Ambient temp. > Tay2
Fan tap
11 Tap
8, 9 or 10 Tap
7, 8 or 9 Tap
Tax1
Tay1
Tax2
Tay2
Tamb: ambient temp. ˚C
Tax1
Tay1
Tax2
Tay2
H1P
H2P
H3P
H4P
H5P
H6P
H7P
26°C
28°C
31°C
33°C
k
h
h
h
h
h
k
20°C
22°C
26°C
28°C
k
h
h
h
h
k
h
27°C
29°C
32°C
34°C
k
h
h
h
k
h
h