Troubleshooting
SiBE811001EB
145
CONVENI-PACK
36
Ti2 thermistor
error
J4
Ti2 thermistor
These conditions continued 300 sec.
—
—
ON if compressor on refrigeration
equipment side is running.
—
ON if AIRNET not present
1
00
Substitute value:
f(LP2) + 5°C (none of the below) or
Ta (mode: 0, 29, 30, 35, 64, 65, 70, 74, 75,
80)
Automatically resets when the following
conditions are met:
Ti2
≤
-43.6°C continued 50 sec.
—
—
—
Automatically resets when
-43.6°C < Ti2 < 55°C continues 10 sec.
37
Ti1 thermistor
error
J5
Ti1 thermistor
These conditions continued 300 sec.
—
—
ON if compressor on refrigeration
equipment side is running.
—
ON if AIRNET not present
1
00
Substitute value:
f(LP2) + 5°C (none of the below) or
Ta (mode: 0, 5, 6, 7, 40, 41, 42)
Automatically resets when the following
conditions are met:
Ti1
≤
-50°C continued for 50 sec.
—
—
—
Automatically resets when -50°C < Ti1 <
55°C continues 10 sec
38
Tce sensor
error
J6
Tce sensor
Tce
≥
90°C continued 50 sec.
—
—
ON if compressor on refrigeration
equipment side is running.
—
ON if AIRNET not present
1
00
Substituted with temperature 1 sec. before
sensor error occurred
Automatically resets when
-43.6°C < Tce < 90°C continues 10 sec.
Tce
≤
-43.6°C continued 50 sec.
—
—
—
39
Tg sensor
error
J9
Tg sensor
These conditions continued 300 sec.
—
—
ON if compressor on cooling
equipment side is running.
—
ON if AIRNET not present
1
00
Substituted with temperature 1 sec. before
sensor error occurred
Automatically resets when
-43.6°C < Tg < 90°C continues 10 sec.
Tg
≤
43.6°C continued 50 sec.
—
—
—
Turn operation switch OFF, or automatically
resets when -43.6°C < Tg < 90°C
40
HP sensor
error
JA
HP sensor
With the operation switch ON, HP
≥
4.3
MPa for 10 min.
—
—
ON if compressor on cooling
equipment side is running.
—
ON if AIRNET not present
1
00
Substitute value: HP = f(Tce)
Automatically resets when
0.01 MPa < HP < 4.3 MPa
With the operation switch ON, HP
≤
0.01
MPa for 10 min.
—
—
—
Substitute value: HP = f(Tce)
41
LP1 sensor
error
JC
LP1 sensor
9
• Compressors running on refrigeration equipment
side stop
• INV. compressor standby: 1 min.
• STD compressor standby: 5 min.
• Retry code "JC" sent to AIRNET
OFF
ON
(5)
OFF
1
(retry code)
5
(JC)
01
Refrigeration equipment side error
Compressors on refrigeration equipment
side stop
Reset the remote controller or the operation
switch, or recycle power
With the operation switch ON,
LP1
≤
-0.05 MPa for 5 min.
4
(Retry count
increments 1
every 5
continuous min.)
Retry code "JC" sent to AIRNET
OFF
OFF
ON if AIRNET not present
(10)
1
(retry code)
10
(JC)
00
Refrigeration side equipment will not start
Automatically resets when
-0.01 MPa < LP1 < 1.8 MPa
42 Inverter error
L1
Inverter PCB
IGBT (
∗
1) alarm detection or INV. error
detected 4 times or more in 1 hour
—
INV. compressor forced stop turns OFF (52C: OFF)
After 1 min., forced OFF is released
OFF
ON
OFF
1
00
System stops
Recycle power
43
INV.
compressor
INV. fin
temperature
rise
L4
Inverter PCB Fin temperature - Fm: 84°C or more
7
• INV. compressor stops
• Standby: 1 - 6 min.
• 8
th
retry, "L4" output to AIRNET
• Compressor max limit is ON during retry attempts
• Retry counter decrements 1 when INV. compressor
runs 1 min. or more total.
• 10
th
retry: INV. compressor stops due to error
ON if compressor on cooling
equipment side is running.
—
—
1
(L4 retry count)
8
(L4 output)
00
"L4" output to AIRNET
Reset the remote controller or the operation
switch, or recycle power
9
OFF
ON if AIRNET not present
(10)
INV. compressor stops due to error
44
INV.
compressor
momentary
overcurrent
L5
Inverter PCB
Overcurrent (65 A DC) flowed through
power transistor
7
• INV. compressor stops
• STD1, STD2 compressors stop
• Standby: 1 - 6 min.
• 8
th
retry: "L5" output to AIRNET
• Retry counter resets when INV. compressor runs 10
min. or more total.
• 10
th
retry: INV. compressor stops due to error
ON if compressor on cooling
equipment side is running.
—
—
1
(L5 retry count)
8
(L5 output)
00
"L5" output to AIRNET
Reset the remote controller or the operation
switch, or recycle power
9
OFF
ON if AIRNET not present
(10)
INV. compressor stops
45
INV.
compressor
overcurrent
L8
Inverter PCB
When compressor overload was detected:
33 A flowed continuously 5 sec.
26 A flowed continuously 260 sec.
7
• INV. compressor stops
• Standby: 1 - 6 min.
• 8
th
retry: "L8" output to AIRNET
• Compressor max limit is ON during retry attempts
• 10
th
retry: INV. compressor stops due to error
ON if compressor on cooling
equipment side is running.
—
—
1
(L8 retry count)
8
(L8 output)
00
"L8" output to AIRNET
Reset the remote controller or the operation
switch, or recycle power
9
OFF
ON if AIRNET not present
(10)
INV. compressor stops
46
INV.
compressor
startup failure
L9
Inverter PCB
When compressor overload was detected:
33 A flowed continuously 5 sec. or
positioning signal disturbance caused by
noise occurred
5 (L9 pre-count)
1 (L9 retry count)
When L9 pre-
count reaches 5
and L9 retry count
is set to 1
• INV. compressor stops
• STD1, STD2 compressors stop
• Standby: ready to restart after 10 sec.
• After 5 pre-counts, "L9" retry count is output to
AIRNET
• Retry counter and pre-counter reset when INV.
compressor runs 1 min. or more total.
• 3rd retry: INV. compressor stops due to error
ON if compressor on cooling
equipment side is running.
—
—
1
(L9 retry count)
2
(L9 output)
00
"L9" output to AIRNET
Reset the remote controller or the operation
switch, or recycle power
2 (L9 retry count)
—
ON if AIRNET not present
(3)
INV. compressor stops
47
INV.
compressor
INV.-to-INV.
transmission
error
LC
Inverter PCB
Transmission has not succeeded for 15
sec. or more.
—
—
ON if compressor on cooling
equipment side is running.
—
ON if AIRNET not present
1
00
"LC" output to AIRNET when no
transmissions for 1 min.
Resets automatically
List of Error Codes (LRYEQ16AY1)
No.
Item
Code
(Remote
controller
display)
Detection
device
Detection conditions
Times of retry
Retry action
R1 signal
Abnormal
stop output
Output during backup
(Only when AIRNET
address is 0)
Times when using
AIRNET output
Sub-classification code
(only for BRC1E1/2/3
remote controllers)
Processing after error is confirmed
Reset procedure
&
OR
&
• SH2 > 35˚C
• Ti2
≥
30˚C
• TgSH > 35˚C
• TdSH2 or TdSH3
<
5˚C
• Ti2
≥
55˚C
OR
• Operating mode: 0, 29, 30, 35, 64,
65, 70, 74, 75, 80
• SH2
<
25˚C
• Ti2
<
30˚C
&
OR
&
• SH1 > 35˚C
• Ti1
≥
30˚C
• TgSH > 35˚C
• TdSH1 or TdSH2
<
5˚C
• Ti1
≥
55˚C
• Operating mode: 0, 5, 6, 7, 40, 41, 42
• SH1
<
25˚C
• Ti1
<
30˚C
OR
&
OR
&
• TgSH > 35˚C
• Tg
≥
30˚C
• SH1 & SH2 > 5˚C
• Y2E_pls > 100
• Tg
≥
55˚C
&
• TdSH1~3
<
5˚C
• Y3E~Y5E_pls > 100
OR
&
&
• LP1
≥
1.8 MPa continued
for 1 min.
• INV. compressor is running
• LP1
≥
1.8 MPa continued for
15 sec.
• STD1 compressor is running