Troubleshooting
SiBE811001EB
245
CONVENI-PACK
8.4.56 Improper Combination of Indoor and Outdoor Units
Error Code
UA
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
The number of indoor units is out of the allowable range.
Error Decision
Conditions
The error decision is made as soon as either of the abnormalities aforementioned is detected.
Supposed
Causes
Excess of connected indoor units
Defective outdoor unit PCB
Troubleshooting
The total of indoor
units displaying "
UA
"
and indoor units
connected to the same
refrigerant system is
within connectable
number of unit.
Does the error reoccur?
Press the RESET button of outdoor
unit PCB for 5 sec.
YES
The number of indoor units that
can be connected to a single
outdoor unit system is excess of
allowable range.
NO
Normal
NO
Replace the outdoor unit main
PCB.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.