SiBE811001EB
Troubleshooting
CONVENI-PACK
198
8.4.22 Outdoor Unit Fan Motor Abnormality
Error Code
E7
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Detect an error for the fan motor circuit based on the number of rotation detected by hole IC
during the fan motor operation.
Error Decision
Conditions
In the condition of fan motor rotation, the number of rotation is below the fixed number for more
than 6 seconds. (System down is caused by 4 times of detection.)
Supposed
Causes
Failure of fan motor
Defect or connection error of the connectors/ harness between the fan motor and PCB
The fan can not rotate due to any foreign substances entangled.
Clear condition: Continue normal operation for 10 minutes