Test Operation
SiBE811001EB
71
CONVENI-PACK
5.9
Check List
[Judgement]
{
: GOOD
: Action item (Operational)
×
: Action item (Not operational)
: GOOD after action
Note) For items not requiring checks, draw a slant line
in the judgement box.
Check item
Check method
Criteria
Actual measurement
Judgement
Operating
data
Outdoor air
temperature
(A)
Measure this temperature using a
thermometer.
(Measure it in places that are no
influence of discharge air from
outdoor unit.)
Refrigeration: -15 to
43°C
Cooling: -5 to 43°C
Heating: -15 to 21°C
–
°C
Suction air
temperature
(B)
Measure this temperature using a
thermometer.
(Check to be sure there is no short
circuit.)
-15 to 43°C
Outdoor unit
°C
Short circuit
value
The above-mentioned (B) - (A) =
∆
t
∆
t
to be within 5 deg.
Outdoor unit
°C
Suction air
temperature of
indoor unit
Use a thermometer.
Cooling: 21 to 32°C
Heating: 15 to 27°C
Indoor unit A
°C
Indoor unit B
°C
Discharge air
temperature of
indoor unit
Use a thermometer.
Cooling: 8 to 17°C
Heating: 30 to 42°C
Indoor unit A
°C
Indoor unit B
°C
Difference of
Suction air
temp. –
Discharge air
temp., both of
indoor unit
Difference of the temperatures
above
Cooling: 8 to 15°C
Heating: 12 to 18°C
Indoor unit A
°C
Indoor unit B
°C
Operation
of indoor
unit
Checking of
water leaks
Check by operating the indoor unit
in cooling mode for a period of 20
minutes or pouring water on the
drain pan.
No water leaks
Indoor unit A
Good / No good
Indoor unit B
Good / No good
Swing
Visual check of the operation using
the indoor unit remote controller
To operate normally.
Indoor unit A
Good / No good
Indoor unit B
Good / No good
Error history
Visual check of the indoor unit
remote controller
History to have been
cleared.
Indoor unit A
Good / No good
Indoor unit B
Good / No good
Others
Fan
Visual check of the fan for rotating
and mounting directions, and for
any obstructions in the air passage
No abnormalities
Outdoor unit
Good / No good
Indoor unit A
Good / No good
Indoor unit B
Good / No good
Abnormal
sounds/
vibrations
Check in the vicinity of casing and
fan by hearing.
No abnormalities
Outdoor unit
Good / No good
Booster unit
Good / No good
Indoor unit A
Good / No good
Indoor unit B
Good / No good
Appearance/
Heat exchanger
Visual check them for any damage,
stain, or else
No defects
Outdoor unit
Good / No good
Booster unit
Good / No good
Indoor unit A
Good / No good
Indoor unit B
Good / No good
Additional
charging volume
of oil
1 liter only when 3 booster
units are installed
Outdoor unit
Good / No good
Additional
charging quantity
of refrigerant
Visual check of oil level through the
sight glass mounted in the liquid
connection piping
Liquid seal
–
Good / No good