8.5.10 Low Pressure Sensor Abnormality
Error Code
JC
Applicable
Models
LCBKQ3AV1
Method of Error
Detection
Error is detected from pressure detected by low pressure sensor.
Error Decision
Conditions
When the low pressure sensor is short circuit or open circuit
(Not less than 1.8MPa, or -0.5MPa and below)
Supposed
Causes
Defective low pressure sensor
Connection of high pressure sensor with wrong connection
Defective outdoor unit PCB
Defective connection of low pressure sensor
Piping with wrong connection
LED Indications
First digit
l l h h l l h
Second digit
l k h l l h h