SiBE811001EB
Troubleshooting
CONVENI-PACK
216
8.4.36 Intermediate/High Pressure Sensor Abnormality
Error Code
J0
,
JA
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Error is detected from pressure detected by high pressure sensor.
Error Decision
Conditions
When the sensor is short circuit or open circuit
(more than 4.22MPa or less than 0.01MPa)
Supposed
Causes
Defective high pressure sensor
Connection of low pressure sensor with wrong connection
Defective outdoor unit PCB
Defective connection of high pressure sensor