SiBE811001EB
Outline of Functions (Outdoor unit)
CONVENI-PACK
80
Case of activating cleaning forcibly
Cooling: All indoor units make their thermostats OFF.
Heating: Forcible shifts to operation mode = 0, 74, 75 and 80 when cleaning request
comes from indoor unit and outdoor unit has approved cleaning.
(1)-4 Outdoor evaporating mode prohibited
(2) Operation instruction of refrigeration/freezing
&
OR
&
&
OR
• Operation mode
≥
43
• Outdoor evaporating mode prohibited (Service mode 2-15): ON
• Tset
≤
16˚C+Correction set 1 (Service mode 2-17)
• Min(Tset – Tr)
≤
2˚C + Correction set 2 (Service mode 2-38)
• Min(Tset – Tr)
≤
4˚C + Correction set 2 (Service mode 2-38)
• Normal mode continues for consecutive 3 hours
• Outdoor evaporating mode prohibited (Service mode 2-15): OFF
• Tset > 16˚C + Correction set 1 (Service mode 2-17)
• Min (Tset – Tr)
≥
6˚C + Correction set 2 (Service mode 2-38)
Tset: Setting temperature of
remote controller
Tr: Indoor suction air temperature
Normal mode
Outdoor evaporating
mode prohibited
OR
OR
OR
OR
• Operation SW: ON
• Compressor re-starting standby terminated
• Main DIP • SW2-2 (Refrigerating forced OFF): OFF
• Main DIP • SW2-2 (Refrigerating forced OFF): ON
• Continuous for consecutive 3 hours have passed
• LP1 > Lpm1 + 0.147MPa
• LP1 > Lpm1(f(Tsd))
• Previous time period of thermostat ON for refrigeration is more than 5 min.
• LP1 > Lpm1(f(Tsd))
• Standby time period for refrigeration is over 3 - 13 min.
• Previous time period of thermostat ON for refrigeration is more than 5 min.
• Outdoor air temperature < Tsd(f(Lpm1))
• Standby time period for refrigeration is over 3 - 13 min.
• Operation SW: OFF
• Low pressure protection for refrigeration activates (
∗
1)
• Refrigerating start terminates (More than 90 seconds after compressor started)
• LP1 < 0.098 MPa
• LP1 < 0.196 MPa continues for 1 min. or more
• INV. compressor is at minimum Hz.
Thermostat OFF
Compressor for
refrigerating OFF
Thermostat ON
Compressor for
refrigerating ON
&
&
OR
OR
∗
1.Low pressure protection conditions for refrigeration
• LP1 < -0.015MPa
• Intermediate SH > 20˚C & 30 sec. have passed
• HP > 1.96MPa & LP1 < 0.049MPa
• LP1 < 0.0245MPa
Tsd: Target of evaporative temperature
(Refer to the field settings)
&
&
&
&
&
&