Troubleshooting
SiBE811001EB
243
CONVENI-PACK
8.4.54 Transmission Error between Main and Sub Remote Controllers
Error Code
U8
Applicable
Models
All indoor models
Method of Error
Detection
In case of controlling with 2-remote controller, check the system using micro-computer if signal
transmission between indoor unit and remote controller (main and sub) is normal.
Error Decision
Conditions
Normal transmission does not continue for specified period.
Supposed
Causes
Defective transmission between main and sub remote controller
Connection between sub remote controllers
Defective remote controller PCB
Troubleshooting
Using 2-remote
controllers control.
SS1 of both remote
controllers is set to
"SUB."
SS1 of remote
controller PCBs is
set to "MAIN."
NO
Set SS1 to "MAIN"; the power
supply OFF once and then
restart.
NO
Turn the power OFF and then
restart. If a malfunction occurs,
replace the remote controller
PCB.
NO
Set one remote controller to
"MAIN"; the power supply OFF
once and then restart.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
YES
YES