SiBE811001EB
Troubleshooting
CONVENI-PACK
156
(1) Monitor mode
No.
Setting Item
LED Display
Data
Display
H1P H2P H3P H4P H5P H6P H7P
0
Abnormality (latest)
l h h h h h h
See next
page
1
System
k h h h h h k
Data
2
Electronic expansion valve
k h h h h k h
Data
3
Pressure sensor
k h h h h k k
Data
4
Thermistor (1)
k h h h k h h
Data
5
Thermistor (2)
k h h h k h k
Data
6
Current sensor
k h h h k k h
Data
7
Protection device
k h h h k k k
Data
8
Transmission system
k h h k h h h
Data
9
Abnormality of the inverter system (1)
k h h k h h k
Data
10 Abnormality of the inverter system (2)
k h h k h k h
Data
11 Abnormality of fan motors
k h h k h k k
Data
14 Details of abnormality (latest)
k h h k k k h
See next
page
15 Abnormality (last but 1)
k h h k k k k
16 Abnormality (last but 2)
k h k h h h h
20 Retry (latest)
k h k h k h h
21 Retry (last but 1)
k h k h k h k
22 Retry (last but 2)
k h k h k k h
The numbers in the "No." column represent the number of times to press the
button.
Press the SET (BS2) button and set the
LED display to a setting item.
Press the MODE (BS1) button in "Setting
mode 1" and set to "Monitor mode."
<Selection of setting item>
<Confirmation on setting contents>
Press the RETURN (BS3) button and
switches to the initial status of the
"Monitor mode."
+
Press the MODE (BS1) button and
returns to "Setting mode 1."
Press the RETURN (BS3) button to
display different data of set items.
SET (BS2)
<Date
-
>
<Date
-
>
Data
k h h h h h k
Detect current reversed phase
k h h h h k h
Detect earth leakage when only INV.
compressor is operating
k h h h k h h
Detect earth leakage when only STD
compressor 1 is operating
k h h k h h h
Detect earth leakage when only STD
compressor 2 is operating
Data
k h h h h h k
Defective the electronic expansion valve (Y1E)
k h h h h k h
Defective the electronic expansion valve (Y2E)
k h h h k h h
Defective the electronic expansion valve (Y3E)
k h h k h h h
Defective the electronic expansion valve (Y4E)
k h k h h h h
Defective the electronic expansion valve (Y5E)
Data
k h h h h h k
Defective the low pressure sensor
for refrigeration (S1NPL1)
k h h h h k h
Defective the low pressure sensor
for air-conditioning (S1NPL2)
k h h h k h h
Defective the high pressure sensor (S1NPH1)
k h h k h h h
Defective the intermediate pressure
sensor (S1NPH2)
Data
k h h h h h k
Defective the discharge pipe thermistor
of the INV. compressor (R31T)
k h h h h k h
Defective the discharge pipe thermistor
of the STD compressor 1 (R32T)
k h h h k h h
Defective the discharge pipe thermistor
of the STD compressor 2 (R33T)
k h h k h h h
Defective the suction pipe thermistor
for refrigeration (R21T)
k h k h h h h
Defective the suction pipe thermistor
for air conditioning (R22T)
Data
k h h h h h k
Defective outdoor air thermistor (R1T)
k h h h h k h
Defective the plate type heat
exchanger outlet thermistor (R4T)
k h h h k h h
Defective the outdoor unit heat
exchanger outlet thermistor (R6T)
Data
k h h h h h k
Defective the current sensor (A5P)
k h h h h k h
Defective the current sensor (A7P)
Data
k h h h h h k
Actuation of the high pressure
switch
k h h h h k h
Actuation of the low pressure switch
Data
k h h h h h k
Defective the inverter transmission
system
k h h h h k h
Displayed while transmitting with the
indoor unit after start-up
k h h h k h h
Defective transmission with the
indoor unit
k h h k h h h
Defective transmission with sub
PCB (A2P)
k h k h h h h
Defective transmission with the
booster unit
k k h h h h h
Defective transmission with the
capacity increasing unit
Data
h h h h h h k
Error "L1" occurs
h h h h h k h
Error "L4" occurs
h h h h k h h
Error "L5" occurs
h h h k h h h
Error "L8" occurs
h h k h h h h
Error "L9" occurs
Data
h h h h h h k
Error "E5" occurs
h h h h h k h
Error "U2" occurs
h h h h k h h
Error "P1" occurs
h h h k h h h
Error "P4" occurs
Data
h h h h h h k
Error "E7" occurs
h h h h h k h
Error "H7" occurs