SiBE811001EB
Troubleshooting
CONVENI-PACK
264
Troubleshooting
∗
1. Voltage measurement point
Refer to P.295.
1.Set the low pressure gauge.
2.Connect a RAM monitor.
Reset the operation, and then restart
the outdoor unit.
Replace the low pressure
sensor.
Are the characteristics
of the low pressure
sensor normal?(
∗
2)
NO
Correct the piping.
Piping for different
circuit is erroneously
connected.
YES
Replace the outdoor unit main
PCB.
YES
Replace the low pressure
sensor.
Are the characteristics
of the low pressure
sensor normal? (Make
a comparison between
the voltage
characteristics (
∗
1)
and the gauge
pressure.)
NO
YES
NO
Replace the outdoor unit main
PCB.
If the PCB pressure
detection normal?
(Make a comparison
between the checker
pressure data and the
voltage characteristics
(
∗
1).)
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Outdoor unit PCB
+5V
GND
Micro-computer
A/D input
∗
2 Measure voltage here.
CHECK 14
Connector for
low pressure
sensor
(X18A)
(4)
(3)
(2)
(1)
Red
Black
White
Low pres
sure sensor
(S1NPL)
CHECK 14