Troubleshooting
SiBE811001EB
161
CONVENI-PACK
Check the contents of abnormalities and retries
Contents of retires and abnormalities are checked as follows.
<Contents of abnormalities and retries>
k
: ON
h
: OFF
l
: Blink
Reference
Code
Contents of Error
Confirmation 1
Confirmation 2
Main content
Details
H1P
H2P
H3P
H4P
H5P
H6P
H7P
H1P
H2P
H3P
H4P
H5P
H6P
H7P
(E1) PCB defect
Defective PCB
l h k h h l l l k h h h h l
(E2) Earth leakage
l k h h h l h
(E3) Actuation of high pressure switch
HPS actuation
l k h h h l l
(E4) Actuation of low pressure sensor
l k h h l h h
(E5) Inverter compressor motor lock
l k h h l h l
(E9)
Defective electronic expansion
valve coil
l k h l h h l
(F3) Abnormal discharge pipe temperature
l h k h l h l l k h h h l l
(H3) Defective high pressure switch
l h k h l h h l k h h h l l
(J3) Defective discharge pipe thermistor
l l k h l l h l k h h h l l
(J8)
Defective heat exchanger inlet
thermistor
l k h l h h h
(J9)
Defective heat exchanger outlet
thermistor
l k h l h h l
(JC) Defective low pressure sensor
l k h l l h h
(L1) Defective inverter PCB
l h k h l l l l k h h h h l
(L4)
Defective inverter radiating fin
temperature rise
Over-heating of the radiation fin
l k h h l h h
(L5)
Momentary overcurrent of inverter
compressor
l k h h l h l
(L8)
Momentary overcurrent of inverter
compressor
l k h l h h h
(L9) Inverter compressor starting failure
l k h l h h l
(LC)
Defective transmission between
inverter and control PCB
l k h l l h h
(P4)
Defective inverter radiating fin
temperature rise sensor
l h k l h h h l k h h l h h
(PJ)
Faulty field setting after replacing main
pcb or faulty combination of PCB
l k h l l h l
(U0) Refrigerant shortage alert
Refrigerant shortage
l h k l h h l l k h h h h h
(U2)
Power supply insufficient or
instantaneous failure
Inverter undervoltage
l k h h h l h
Open phase in inverter (T-phase)
Abnormal charging of the main
circuit condenser
(U4)
Defective transmission between
outdoor units and booster units
Defective indoor/outdoor
transmission
l k h h l h h
Defective the indoor system
(UF) System is not set yet
l k h l l l l
(UH)
Defective refrigerant system
address undefined
l k h l h l l
∗
1: Either short circuit or open.
<Selection of retry or abnormality item>
<Display Confirmation 1>
<Display Confirmation 2>
Press the BS1 (MODE) button in
"Setting mode 1" switches to "Monitor
mode."
Press the BS2 (SET) button to indicate
confirmation 2 on the lamp display.
∗
Press the MODE (BS1) button and
returns to "Setting mode 1."
Press the SET (BS2) button and
select a monitoring item No. 0, 14, 15,
16 to check the lamp display.
Press the BS3 (RETURN) button to
indicate confirmation 1 on the lamp
display.
Press the BS3 (RETURN) button to
switch to the initial status of the
"Monitor mode."
First digit
Second digit
Display of Error codes