SiBE811001EB
Troubleshooting
CONVENI-PACK
176
8.4.8 Electronic Expansion Valve Error / Dust Clogging
Error Code
A9
Applicable
Models
FXFQ
Method of Error
Detection
Check coil condition of electronic expansion valve by using micro-computer.
Check dust clogging condition of electronic expansion valve main body by using micro-
computer.
Error Decision
Conditions
Pin input for electronic expansion valve coil is abnormal when initializing micro-computer.
Either of the following conditions is seen/caused/ occurs while the unit stops operation.
z
Temperature of suction air (R1T) – temperature of liquid pipe of heat exchanger (R2T) > 8°C.
z
Temperature of liquid pipe of heat exchanger (R2T) shows fixed degrees or below.
Supposed
Causes
Defective electronic expansion valve coil
Defective of indoor unit PCB
Defective relay cables