Test Operation
CONVENI-PACK
74
[Judgement]
{
: GOOD
: Action item (Operational)
×
: Action item (Not operational)
: GOOD after action
Note) For items not requiring checks, draw a slant line
in the judgement box.
Model name
Serial No.
System name / Installation place
Outdoor unit
Booster unit
Indoor unit A
Indoor unit B
Check item
Check method
Criteria
Actual measurement
Judgement
Field
connection
wiring
Individual
breaker–
External power
supply line
Visual check
No reverse phases
Good / No good
Transmission
line between
units
Visual check
No errors in wiring (terminal)
Good / No good
Transmission
line between
control boards
Visual check
No errors in wiring (terminal)
Good / No good
Low voltage
wiring
Between units: Check between
terminals (A) and
(C)
Between control boards:
Check between
terminals (T1) and
(T2)
High voltage and low voltage wires are to
be wired separately (at a distance of 50
mm or more from each other).
Good / No good
Ground wire
Visual check
To be connected (B/U & external unit).
Good / No good
Refrigerant
piping
Mounting of sight
glass
Visual check
To be mounted to liquid piping.
Good / No good
To be mounted to riser or horizontal piping.
Good / No good
Mounting of drier
filter
Visual check
To be mounted to liquid piping.
Good / No good
B/U piping
Visual check
The piping lengths both on the discharge piping
and suction piping are to be within 30 m.
Good / No good
The difference of elevation for the installation
of B/Us is to be 10 m or less from the floor
level on which the S/C is installed.
Good / No good
Internal
refrigerant
system
Check welded, flared, and flanged
sections in internal refrigerant
piping with a leak tester.
No leaks
Good / No good
Heat insulation
work on
connection
piping
Visual check
Outdoor unit: Air conditioning
Liquid
10mm
Gas
20mm
Refrigeration
Liquid
20mm
Gas
30mm
Good / No good
B/U:
Discharge
10mm
Suction
50mm
Liquid inlet
20mm
Liquid outlet
30mm
Good / No good
Insulation
measurement
Compressor
Measure with a 500V megger
tester.
(Measure at U, V, and W phases
and then record a minimum value.)
1 M
Ω
or more
Inverter
compressor
M
Ω
Standard
compressor
M
Ω
Standard
compressor
M
Ω
Booster unit
M
Ω
Fan motor
Measure with a 500V megger
tester.
1 M
Ω
or more
Outdoor unit
MF1
M
Ω
MF2
M
Ω
Indoor unit A
M
Ω
Indoor unit B
M
Ω
Power supply
circuit
Measure with a 500V megger
tester.
(Measure at U, V, and W phases
and then record a minimum value.)
1 M
Ω
or more
Outdoor unit
M
Ω
Booster unit
M
Ω
Indoor unit A
M
Ω
Indoor unit B
M
Ω