Standard Specification
SiBE811001EB
27
CONVENI-PACK
(29)
Gauge port
—
Used to connect the low pressure gauge on the refrigeration side.
(30)
Stop valve (air conditioning
side) (liquid)
—
For liquid (air conditioning side)
(31)
Stop valve (air conditioning
side) (gas)
—
For gas (air conditioning side)
(32)
Stop valve (refrigeration
side) (liquid)
—
For liquid (refrigeration side)
(33)
Stop valve (refrigeration
side) (gas)
—
For gas (refrigeration side)
(34)
Stop valve (for
maintenance) (gas)
—
Confines the liquid refrigerant volume to be recovered by closing at the time
of maintenance.
(35)
Stop valve (for
maintenance)
(intermediate)
—
Confines the liquid refrigerant volume to be recovered by closing at the time
of maintenance.
(36)
Thermistor (discharge
pipe)
R31T
Used to detect the discharge pipe temperature of the INV. compressor
(M1C) and control this compressor (M1C) for protection.
(37)
Thermistor (discharge
pipe)
R32T
Used to detect the discharge pipe temperature of the STD compressor 1
(M2C) and control this compressor (M2C) for protection.
(38)
Thermistor (discharge
pipe)
R33T
Used to detect the discharge pipe temperature of the STD compressor 2
(M3C) and control this compressor (M3C) for protection.
(39)
Thermistor (plate type heat
exchanger outlet)
R4T
Used to detect the liquid refrigerant temperature, and control subcooling.
(40)
Thermistor (outdoor unit
heat exchanger outlet)
R6T
Used to control the superheated exchange with a plate type heat
exchanger.
(41)
Thermistor (suction pipe)
(refrigeration side)
R21T
Used to detect the suction pipe temperature on the air conditioning side
control compressor for protection.
(42)
Thermistor (suction pipe)
(air conditioning side)
R22T
Used to detect the suction pipe temperature on the refrigeration side control
compressor for protection.
(43)
Thermistor (outdoor air)
R1T
Used to detect the outdoor air temperature and control the fan operation.
(44)
Solenoid valve
(subcooling)
Y1S
Performs open/close for subcooling control of liquid refrigerant.
(45)
Solenoid valve (gas vent
pipe)
Y6S
Performs open/close to keep the pressure in receiver.
No.
Name
Electric
symbol
Function