SiBE811001EB
Troubleshooting
CONVENI-PACK
230
Refer to P.291.
Cancel the melting state of
refrigerant.
Refrigerant is melting.
(The unit is out of power supply for
more than 6 hours.)
Recheck the compressor/
refrigerant circuit.
NO
YES
Continued from the previous page.
(Start failure due to aged operation.)
YES
Replace the inverter
compressor.
Check if the insulation
resistance of the compressor
is 100k
Ω
or more.
NO
YES
Replace the compressor
inverter PCB (A4P).
Check if the power
transistor is normal.
NO
Replace the inverter
compressor.
Broken inside the
compressor
YES
NO
CHECK 4
CHECK 4