SiBE811001EB
Field Setting
CONVENI-PACK
112
(11) <Setting method of the outdoor unit fan control at snow>
When the operation mode is "0, 64, 65, 70", the outdoor unit fan can regularly be driven.
The numbers
"
42
"
represent the number of times to press the BS2 button to select each setting
h
Control specification
, Set 0 (factory setting); The outdoor unit fan is normally controlled.
The outdoor unit fan has stopped at mode of operation "0, 64, 65, 70".
, Set 1;
k
Driving condition of the outdoor unit fan
• At operation mode 0;
• At operation mode 64, 65, 70;
k
Control specification
• Fan tap = 4 is maintained for 1 minute.
, Set 2;
k
Driving condition of the outdoor unit fan
• At operation mode 0;
• At operation mode 64, 65, 70;
k
Control specification
• Fan tap = 7 is maintained for 1 minute.
, Set 3
k
Driving condition of the outdoor unit fan
• At operation mode 0;
• At operation mode 64, 65, 70;
k
Control specification
• Fan tap = 4 is maintained for 1 minute.
No.
Display of setting items
Display of setting conditions
Setting item
H1P H2P H3P H4P H5P H6P H7P
3-42
Setting method of the outdoor unit
fan control at snow
k
k
h
k
h
k
h
&
Fan tap = 0 passes continuous 30 minutes.
Outdoor temperature <5°C
Fan tap = 0 passes continuous 30 minutes.
Outdoor air temperature <5°C
&
Fan tap = 0 passes continuous 30 minutes.
Outdoor air temperature <5°C
Fan tap = 0 passes continuous 30 minutes.
Outdoor air temperature <5°C
&
Fan tap = 0 passes continuous 30 minutes.
Outdoor air temperature <5°C
Fan tap
≤
3 passes continuous 30 minutes.
Outdoor air temperature <5°C
H1P
H2P
H3P
H4P
H5P
H6P
H7P
Set 0: (Factory setting)
k
h
h
h
h
h
k
Set 1
k
h
h
h
h
k
h
Set 2
k
h
h
h
k
h
h
Set 3
k
h
h
k
h
h
h