Troubleshooting
SiBE811001EB
191
CONVENI-PACK
Troubleshooting
Reset the power with the
operation switch set to OFF.
Earth leakage (breaker
ON/OFF): E2
NO
Replace the defective parts.
Earth leakage (leakage detector
PCB): E2
NO
Replace the defective parts.
Earth leakage (leakage detector
PCB): E2
NO
Correct connection.
NO
Replace the leakage detector
PCB.
NO
Replace the leakage detector
PCB.
NO
Replace the high pressure
switch.
NO
It is likely that earth leakage
occurred due to temporary liquid
return or refrigerant slugging.
Earth leakage is possible in the
event of power failure during
operation or prolonged power
shutoff.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
YES
YES
YES
YES
YES
YES
More than 10
seconds passed
since power-ON.
Shut OFF power.
Remove the compressor lead wire.
No defective insulation
on compressor
No defective
insulation on entire
product
High pressure
switch is properly
connected.
Leakage detector
PCB fuse is not
blown.
Leakage detector
PCB is energized.
High pressure
switch is energized
at both ends.
Recover all wiring.
Turn ON the power.