Troubleshooting
SiBE811001EB
165
CONVENI-PACK
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Provide 200V power supply.
NO
YES
Is power supply
200V provided?
NO
YES
The float switch is
connected to X8A
of the indoor unit
PCB.
YES
The float switch
contact is forming a
short circuit
(continuity check with
X8A disconnected)
NO
NO
YES
NO
YES
YES
NO
YES
NO
Water builds up
in the drain pan.
The drain pump is
connected to X25A
or terminals Y1 and
Y2 of the indoor
unit PCB.
The drain pump
works when the
power supply is
reset for the
indoor unit.
The voltage of
terminals Y1 and Y2
or X25A is 200V
(within 5 minutes of
resetting the power
supply).
A short circuit
connector is
connected to X8A.
NO
NO
Becomes normal when
X8A of the indoor unit
PCB is short circuited.
YES
YES
NO
YES
The float switch
functions normally.
Connect either a short circuit
connector or float switch and
turn ON again.
Defective indoor unit PCB.
Loose connection of connector.
Replace the float switch.
Modify the float switch's
connection and turn ON again.
Connect the drain pump and
turn ON again.
Replace the drain pump or
check for dirt, etc.
Check the drain piping for
clogging or upward slope, etc.
Replace the indoor unit PCB.