Test Operation
SiBE811001EB
53
CONVENI-PACK
5.2.3 Checking the Operation Data
[Judgement]
{
: GOOD
: Action item (Operational)
×
: Action item (Not operational)
: GOOD after action
Note) For items not requiring checks, draw a slant line
in the judgement box.
ZEAS-AC
Model name
Serial No.
System name / Installation place
Outdoor unit
Booster unit
Indoor unit A
Indoor unit B
Check item
Check method
Criteria
Actual measurement
Judgement
Field
connection
wiring
Individual
breaker–
External power
supply line
Visual check
No reverse phases
Good / No good
Transmission
line between
units
Visual check
No errors in wiring (terminal)
Good / No good
Transmission
line between
control boards
Visual check
No errors in wiring (terminal)
Good / No good
Low voltage
wiring
Outdoor unit:
Check between X3M terminals (1)
and (2),
X1M on A1P,
To the indoor unit, between
(F1) and (F2)
To the outdoor unit, between
(F1) and (F2)
X6M terminal between (L1) and (L2)
Booster unit:
Check between X2M terminals (1)
and (2)/(T1) and (T2)/(F1) and (F2)
High voltage and low voltage wires are to
be wired separately (at a distance of 50
mm or more from each other).
Good / No good
Ground wire
Visual check
To be connected (B/U & outdoor unit).
Good / No good
Refrigerant
piping
Mounting of sight
glass
Visual check
To be mounted to liquid piping.
Good / No good
To be mounted to riser or horizontal piping.
Good / No good
Mounting of drier
filter
Visual check
To be mounted to liquid piping.
Good / No good
Outdoor unit
piping
Visual check
Must be within 130m for both liquid and
gas pipes. The difference in height
between indoor and outdoor units should
be 35m or less when the outdoor unit is
above, 10m or less when it is below.
Good / No good
B/U piping
Visual check
The piping lengths both on the discharge piping
and suction piping are to be within 30 m.
Good / No good
The difference of elevation for the installation
of B/Us is to be 10 m or less from the floor
level on which the S/C is installed.
Good / No good
Internal
refrigerant
system
Check welded, flared, and flanged
sections in internal refrigerant
piping with a leak tester.
No leaks
Good / No good
Heat insulation
work on
connection
piping
Visual check
Outdoor unit: Air conditioning
Liquid
10mm
Gas
20mm
Refrigeration
Liquid
20mm
Gas
30mm
Good / No good
B/U:
Discharge
10mm
Suction
50mm
Liquid inlet
20mm
Liquid outlet
30mm
Good / No good