Troubleshooting
SiBE811001EB
185
CONVENI-PACK
8.4.14 Discharge Air Thermistor Abnormality
Error Code
CA
Applicable
Models
FXMQ
Method of Error
Detection
Error detection is carried out by temperature detected by discharge air thermistor.
Error Decision
Conditions
When the thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Wiring defect
Defective thermistor
Defective indoor unit PCB
Troubleshooting
Refer to P.293.
Remove the discharge air thermistor
(R4T) from the indoor unit PCB, and
then insert it again.
NO
Is the operation normal?
Is it normal?
5 k
Ω
to 90 k
Ω
Remove the thermistor from the
indoor unit PCB, and then make
resistance measurement of the
thermistor using a multiple meter.
Replace the thermistor (R4T).
NO
Normal (The error is caused by
defective contact.)
YES
Replace the indoor unit PCB.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
CHECK 13
CHECK 13