Troubleshooting
SiBE811001EB
303
CONVENI-PACK
(7) Once steps (1) to (6) have been followed and set-up accordingly, the booster information should be displayed in the
"BU1:0" section as shown below (left).
∗
The below display is in the event that the value "3" was recorded in step (1), and although the values under
"BU1:0" are all "0", in reality this section will display the various temperatures and pressures of the booster.
For the various definitions for this information, refer to the table outlined below (right).
Error data information
Definitions
Error data
*Refer to table below
Run mode - 52C
Highest order bit: operating mode
(0/1), lowest order bit: 52C (0/1)
EV(/2)
Degree of opening in the booster's
Y1E ½ display (0 to 240 Pls)
Y2E(/2)
Degree of opening in the booster's
Y2E ½ display (0 to 240 Pls)
Td1
Booster discharge pipe
temperature
Tl
Booster double pipe heat
exchanger inlet temperature
Tg
Booster double pipe heat
exchanger outlet temperature
Teg
Booster evaporating temperature
Target LP
Booster target evaporating
temperature equivalent pressure
INV. frequency
(3 times)
INV. rps display
INV. secondary
current
Booster secondary current
* The Qup/BS (193) distinguishes between the Qup and booster.
For the booster: 192 - 196, with all other values being the booster's.
This will differ depending on the settings or number of boosters
connected.
Error code
Ram
monitor
display
Error code
Ram
monitor
display
E1
31
L4
74
E2
32
L5
75
E3
33
L8
78
E4
34
L9
79
E5
35
LC
7C
E9
39
P1
81
F3
53
P4
84
H3
43
PJ
8D
J3
63
U0
90
J8
68
U2
92
J9
69
U4
94
JC
6C
UF
9F
L1
71
UH
9B