SiBE811001EB
Troubleshooting
CONVENI-PACK
256
Troubleshooting
∗
1. Make a comparison between the voltage of the pressure sensor and that read by the pressure gauge.
∗
2. Make measurement of voltage of the pressure sensor.
∗
3. Checking the clog
To check for the presence of clog, measure the pipe temperature at the location before and after the check point.
(1) Electronic expansion valve
(2) Secondary equipment filter
(3) Outdoor unit filter
Refer to P.286, 287.
Is the stop valve open?
Are the
characteristics of
the low pressure
sensor normal?
(See
∗
1.)
Check if the “low
pressure” value and the
actual measurement
value by pressure
sensor are the same.
Open the stop valve.
NO
Replace the low pressure
sensor.
NO
Replace the outdoor unit main
PCB (A1P).
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
YES
YES
YES
(1) Mount a pressure gauge on the low
pressure service port.
(2) Reset the operation and then
restart the operation.
Service Checker
Connect the service checker to compare the “low pressure” value and
the actual measurement value by pressure sensor (Refer to
∗
1) by
using the service checker.
· The low pressure sensor is normal, and the pressure detected with
the PCB is also normal.
· The low pressure has really become low.
CHECK 2-1, 2-2
Referring to information, remove the causes by
which the low pressure has become low.
At first, check the clogging of refrigerant system. (
∗
3)
+5V
Connector for low pressure sensor
Micro-computer
A/D input
Red
Black
White
Low
pressure
sensor
(4)
(3)
(2)
(1)
(Blue)
X18A
Make measurement of DC voltage between these wires.
CHECK 2-1, 2-2