8.4.42 Momentary Overcurrent of Inverter Compressor
Error Code
L5
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Error is detected from the current flowing in the power transistor.
Error Decision
Conditions
When an excessive current (32.3A) flows in the power transistor
Supposed
Causes
Defective compressor coil (disconnected, defective insulation)
Compressor start-up error (mechanical lock)
Defective inverter PCB
Troubleshooting
Refer to P.291.
YES
YES
CHECK 4
Power OFF
Power OFF
Power ON
(
)
Replace the inverter PCB.
Check if the stop
valve is open.
Check if the
compressor lead wires
are normal.
Check if the wiring
and connection to the
compressor are
normal.
Insulation resistance
of the compressor is
100 k
Ω
or less.
Compressor coils are
disconnected.
Failure occurs again
after restarting the
unit.
Failure occurs again
after restarting the unit.
YES
YES
YES
YES
YES
NO
NO
Check if the power transistor
is normal.
Open the stop valve.
NO
Replace compressor lead wires.
NO
Correct the wiring and
connection.
Replace the inverter
compressor.
Replace the inverter
compressor.
NO
Replace the inverter PCB.
NO
Continue the operation.
Momentary power failure is
possible.
NO
Continue the operation.
NO
Replace the inverter
compressor.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.