Troubleshooting
SiBE811001EB
307
CONVENI-PACK
8.7
Troubleshooting by RAM Monitor (Booster Unit)
Using the RAM monitor makes it possible to check the following operating data.
<Mode 1>
[Main]
[Mode]
[outdoor_unit_data]
[Sensor]
SP_No.
SP number
Ver.
Version of software
operation_SW
Operating switch ON/OFF (OFF/ON: 0/1)
thermostat_SW
Refrigerating thermostat input (AC input) ON/OFF (OFF/ON: 0/1)
Mode
ON/OFF: 1/0
Next_mode
Next operating mode to be transitioned
Before_mode
Operating mode prior to current operating mode
Mode_complete
Flag for the completion of mode change-over (incomplete/complete: 0/1)
Bu_thermostat_ON
Bu thermostat condition (ON/OFF: 1/0)
outdoor_unit_thermostat_ON
Outdoor thermostat condition transmitted from the outside (Comp condition) (ON/OFF: 1/0)
Bu_driving_permission
Displaying the Bu operating permission transmitted from the outside (0/1)
LP1 (outdoor_unit)
Low pressure sensor value of the outdoor unit transmitted from the outdoor unit (20 sec.
intervals)
Td1
R31T
Discharge pipe temperature thermistor value
LP
SINPL
Low pressure sensor value
Tg
R6T
Double tube heat exchanger inlet thermistor
HP_prediction
—
Predicted HP
Teg
—
Evaporating temperature
TI
R4T
Plate type heat exchanger outlet thermistor