SiBE811001EB
Troubleshooting
CONVENI-PACK
218
8.4.37 Low Pressure Sensor Abnormality
Error Code
J1
,
JC
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Error is detected from pressure detected by low pressure sensor.
Error Decision
Conditions
When the sensor is short circuit or open circuit
(more than 1.77MPa or less than -0.01MPa)
Supposed
Causes
Defective low pressure sensor
Connection of high pressure sensor with wrong connection
Defective outdoor unit PCB
Defective connection of low pressure sensor
Mismatched connection with piping