SiBE811001EB
Troubleshooting
CONVENI-PACK
250
8.4.60 System Abnormality and Refrigerant System Address Undefined
Error Code
UH
Applicable
Models
All indoor models
LRYEQ16AY1
Method of Error
Detection
Detect an indoor unit with no address setting.
Error Decision
Conditions
The defective decision is made as soon as the abnormality aforementioned is detected.
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units and outdoor-
outdoor units
Defective indoor unit PCB
Defective outdoor unit PCB
Troubleshooting
∗
1. Check the correct wiring “indoor-outdoor” and “outdoor-outdoor” by Installation manual.
NO
YES
YES
YES
Normal
NO
NO
After fixing the incorrect wiring,
press and hold the RESET
button on the master outdoor
unit PCB for 5 seconds.
∗
The unit will not run for up to
12 minutes.
NO
Normal
NO
Replace the indoor unit PCB.
Replace the outdoor unit PCB.
YES
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Is electricity being introduce
for the first time after
installation or after an indoor
or outdoor unit PCB has
been replaced?
Does an error occur even
after 12 minutes elapses
from the time when
electricity is introduced to
indoor and outdoor
units?
Is indoor - outdoor and
outdoor - outdoor unit
transmission wiring
normal?
∗
1
Does a “
UH
” error
occur for all indoor
units in the system?
Does an error reoccur?
Press and hold the RESET button on
the outdoor unit PCB for 5 seconds.