SiBE811001EB
Troubleshooting
CONVENI-PACK
174
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
YES
NO
Provide 200V power supply.
NO
NO
NO
YES
YES
YES
NO
YES
NO
NO
YES
NO
YES
Replace the indoor unit PCB.
Connect the connector to X9A
and turn ON again.
Replace the swing motor.
Replace the limit switch relay
cable.
Replace the indoor unit PCB.
Replace the power supply relay
cable.
Replace the swing motor.
Take the cam mechanism apart,
reassemble and turn ON again.
Is power supply
200V provided?
The swing motor
works when the
power supply is
turned OFF and
then restart.
The connector is
connected to X9A
of the indoor unit
PCB.
The limit switch
functions normally.
The relay cable is
short-circuited or
disconnected.
After turning the
swing-flap ON and
then stopping with the
remote controller, the
voltage of X6A of the
indoor unit PCB is
200 VAC when
turned ON again
(within 30 seconds of
turning ON again).
The relay cable has
no continuity.
When the airflow
direction flap-cam
mechanism is
disconnected from
the swing motor,
operation is normal
when turned ON
again.
YES
YES
NO
Indoor unit is a
model equipped
with a swing flap
function.