SiBE811001EB
Troubleshooting
CONVENI-PACK
240
Troubleshooting
Reset the power supply.
Check if indoor unit PCB or
outdoor unit PCB has been
replaced. Or check if
indoor/outdoor, outdoor/
outdoor relay wires has
been modified.
Check if all the indoor
remote controllers within
the same refrigerant circuit
display “
U4
”.
Check if the indoor/
outdoor, outdoor/ outdoor
relay wires are normal.
NO
YES
Replace the indoor unit PCB.
Press the RESET button on the
outdoor unit main PCB of the
master outdoor unit. Keep
pressing for 5 seconds or more.
(Operation does not start for a
maximum 12 minutes.)
Caution) Operation switch is only in
the OFFs take, RESET
button will not be accepted.
Always, please check that
operation switch is OFF.
YES
Press the RESET button on the
outdoor unit main PCB of the
outdoor unit. Keep pressing for 5
seconds or more.
NO
Correct the relay wires.
NO
Replace the outdoor unit main
PCB.
YES
Check if the normal
condition monitor for the
micro-computer (HAP) on
the outdoor unit PCB
blinks.
Check if the indoor/
outdoor, outdoor/ outdoor
relay wires are normal.
Check if the operation
is normal with 1 circuit
after outdoor/outdoor
relay wires are
disconnected.
Check if the voltage
between R, S terminals on
the outdoor unit PCB is
200V.
NO
Correct the voltage (200V).
NO
Check if the LED in
preparation mode (H2P)
on the outdoor unit PCB
blink.
Lights do not go out for
12 minutes or more.
The fuse on the outdoor
unit PCB is blown.
NO
Replace the fuse.
YES
Install DIII-Net extension
adaptor.
YES
Correct the connecting wires.
NO
Replace the outdoor unit PCB.
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
NO
YES
YES
YES
YES
NO
YES