8.4.35 Outdoor Air Thermistor Abnormality
Error Code
H9
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Error is detected from the temperature detected by the outdoor air thermistor.
Error Decision
Conditions
When the outdoor air temperature thermistor has short circuit or open circuit
Supposed
Causes
Defective thermistor connection
Defective outdoor air thermistor
Defective outdoor unit PCB (A1P)
Troubleshooting
Refer to P.293.
YES
Check if connector is connected to
X18A of outdoor unit PCB (A1P).
Resistance is measured with a tester
after disconnecting the thermistor
from the outdoor unit PCB.
Is it normal?
Is the resistance normal?
Connect correctly.
NO
Replace the outdoor air
thermistor (R1T).
NO
Replace the outdoor unit PCB
(A1P).
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
CHECK 13