Troubleshooting
SiBE811001EB
227
CONVENI-PACK
Troubleshooting
Output current check
Refer to P.291.
YES
YES
CHECK 4
Power OFF
Connect the compressor lead wires
then restart the operation.
Check if the stop
valve is open.
Check if the
compressor lead wires
are normal.
Check if the wiring
and connection to the
compressor are
normal.
Insulation resistance
of the compressor is
100k
Ω
or less.
Compressor coils are
disconnected.
Check if the pressure
difference between
high pressure and
low pressure before
restarting is 0.2MPa
or less.
Error code “
L8
” is
displayed again.
YES
YES
YES
YES
YES
NO
NO
Check if the power transistor
is normal.
Open the stop valve.
NO
Replace the compressor lead
wires.
NO
Correct the wiring and
connection.
Replace the inverter
compressor.
Replace the inverter
compressor.
NO
Replace the compressor inverter
PCB (A4P).
NO
Defective pressure equalizing in
the refrigerant circuit.
NO
Continue the operation.
NO
Inspection of the compressor.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
CHECK 4