Outline of Functions (Outdoor unit)
CONVENI-PACK
78
(2) Step control of outdoor unit
<Compressor step table (for refrigeration)>
<Outdoor unit fan step table>
INV.
step
INV. compressor frequency
(No. of revolution)
(Hz)
(rps)
0
0
0
1
52
26
2
56
28
3
62
31
4
68
34
5
74
37
6
80
40
7
88
44
8
96
48
9
104
52
10
110
55
11
116
58
12
124
62
13
132
66
14
144
72
15
158
79
16
165
82.5
17
176
88
18
188
94
19
202
101
20
210
105
Fan tap
0
1
2
3
4
5
6
7
8
9
10
11
Revolution of outdoor unit fan
(standard setting)
(rpm)
0
300
460
690
460
570
720
800
930
1050
1091
1186
0
0
0
0
395
540
690
770
900
1020
1061
1156
Fan tap
0
1
2
3
4
5
6
7
8
9
10
11
Revolution of outdoor unit fan
(high static pressure setting)
(rpm)
0
300
460
690
460
570
720
800
930
1136
1186
1235
0
0
0
0
395
540
690
770
900
1106
1156
1205