Troubleshooting
SiBE811001EB
209
CONVENI-PACK
8.4.30 Wet Operation from Injection Pipe
Error Code
F5
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Detect an error for discharge SH and suction SH of driving compressor
Error Decision
Conditions
These conditions continued for 10 minutes.
Supposed
Causes
Defective electronic expansion valve (Y2E~Y5E)
Defective plate type heat exchanger outlet thermistor (R4T)
Defective suction pipe thermistor (R21T, R22T)
Refrigerant overcharge
Troubleshooting
&
Suction SH of refrigeration side > 5K
Discharge SH < 10K
Discharge pipe temperature < 60°C
Wrong
wiring of
electronic expansion
valves (Y2E~Y5E), defective
electronic expansion valve body
(Y2E~Y5E), defective coil,
or disconnected
coil
Disconnected
plate type heat
exchanger outlet thermistor
(R4T), defective thermal
insulation, or defective
resistance value
YES
Repair the defective parts.
Repair the defective parts.
Check whether charging
amount of refrigerant
onsite is appropriate.
YES
Repair the defective parts
Correct the cause of wet
operation on refrigeration
side. (Refer to the “
F4
” flow)
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
NO
NO
NO
Disconnected
suction thermistor
(R21T, R22T), defective thermal
insulation, or defective
resistance
value