![Daikin LCBKQ3AV1 Service Manual Download Page 260](http://html.mh-extra.com/html/daikin/lcbkq3av1/lcbkq3av1_service-manual_501887260.webp)
Troubleshooting
SiBE811001EB
259
CONVENI-PACK
8.5.6 Error Electronic Expansion Valve Coil
Error Code
E9
Applicable
Models
LCBKQ3AV1
Method of Error
Detection
To be detected based on continuity existence of electronic expansion valve coil when the power
supply is ON.
Error Decision
Conditions
No current is detected in the common (COM [+]) when power supply is ON.
Supposed
Causes
Disconnection of connectors for electronic expansion valve (Y1E or Y2E)
Defective electronic expansion valve coil
Defective outdoor unit main PCB
Troubleshooting
∗
1. Make measurement of resistance between the connector pins, and then make sure the resistance falls in the range of 40 to
50
Ω
.
LED Indications
First digit
l h k h h l l
Second digit
l k h l h h l
External factor other than error
(for example, noise etc.).
YES
Ensure correct connection.
NO
Replace the electronic
expansion valve coil.
NO
Replace the PCB (A1P).
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Turn power supply OFF, and turn
power supply ON again.
Return to normal?
NO
YES
The connector of
outdoor unit PCB (A1P)
for electronic expansion
valve is connected.
The coil resistance of
electronic expansion
valve is normal. (
∗
1)
(Orange) 1
(Red) 2
(Yellow) 3
(Black) 4
5
COM[+] (Gray) 6
Measuring points
1 - 6
2 - 6
3 - 6
4 - 6
Judgement criteria
40~50
Ω