SiBE811001EB
Troubleshooting
CONVENI-PACK
280
Troubleshooting
Refer to P.291.
There are problems
on the condition of
power supply
described above.
The insulation resistance
of compressor is not more
100k
Ω
.
The insulation
resistance of fan motor
is not more 1M
Ω
.
CHECK 4
Stop (standby) before
the fan rotates.
Check the condition of the power
supply.
Check if power supply voltage is
200V ± 10%.
Check if there is open phase or
defective wiring.
Check if power supply voltage side
unbalance is within 5V.
Turn ON the power supply, and start
operation.
NO
NO
NO
NO
NO
YES
Is the power transistor
normal?
Correct the fault.
YES
Replace the compressor.
YES
Replace the inverter PCB.
NO
Replace the fan motor.
If the fan motor is badly
damaged, replace the
inverter PCB.
YES
Replace the noise filter PCB.
(Defective noise filter)
YES
The “
U2
” error recurs.
Check the harness.
YES
Stop (standby) when
the compressor
starts up.
Replace the inverter PCB.
∗
If the inverter PCB is badly
damaged, recheck the
compressor.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Continue the operation.
∗
Causes: Instantaneous
power failure (open phase),
noises, or else.
NO
CHECK 4