Troubleshooting
SiBE811001EB
143
CONVENI-PACK
14
Communicati
on error
(Outdoor -
Booster)
EH
Outdoor unit
main PCB
When transmission between outdoor unit
and booster unit is not carry out normally
for a certain amount of time.
—
—
ON if compressor on refrigeration
equipment is running.
—
ON if AIRNET not present
1
00
—
Reset automatically
Check the power supply for booster and
outdoor unit.
Check the transmission wire.
15
Booster error
judgement
EJ
Booster error
stop
Booster error confirmed
See BU error list See BU error list
ON if compressor on refrigeration
equipment is running.
—
ON if AIRNET not present
See BU error list
00
Output when booster failure changes to a
confirmed error
Return to normal state, then recycle power
or reset the operation switch.
16
Shortage of
refrigerant
F3
Thermistor on
each
discharge pipe
Opening
degree of
Y2E - Y5E
3
—
ON if compressor on refrigeration
equipment is running.
—
—
—
00
—
Reset the remote controller or the operation
switch, or recycle power
4
NON2 compressor stops due to error
—
ON if AIRNET not present
(4)
4
STD2 compressor stops due to error
6
NON1 compressor stops due to error
—
ON if AIRNET not present
(6)
6
STD1 compressor stops due to error
8
INV. compressor stops due to error
OFF
ON (8)
OFF
8
INV. compressor stops due to error
17
INV.
discharge
pipe
temperature
retry
F3
Discharge
pipe
thermistor (for
INV.)
Td1 was 150°C or higher
—
—
ON if compressor on refrigeration
equipment is running.
—
ON if AIRNET not present
1
10
INV. compressor error is confirmed
(confirmed on 1
st
occurrence)
Recycle power, or reset the operation
switch.
9
• Td1 = 100°C & standby time: 1.5 - 6 min.
• 10
th
retry: "F3" is output to AIRNET
• During retries, target Td1 limitation exists
• Retry counter decrements 1 when INV. compressor
runs 10 min. or more total.
• 15
th
retry: INV. compressor stops due to error
—
—
1
[F3 retry code]
10
(F3 output)
—
14
—
ON if AIRNET not present
(15)
INV. compressor stops due to error
18
STD1
discharge
pipe
temperature
retry
F3
Discharge
pipe
thermistor
(for STD1)
Td2 was 150°C or higher
—
—
—
ON if AIRNET not present
1
11
STD1 compressor error is confirmed
(confirmed on 1
st
occurrence)
9
• Td2
≤
100°C & standby time: 3 - 10 min.
• 10
th
retry: "F3" is output to AIRNET
• During retries, target Td2 limitation exists
• Retry counter decrements 1 when STD1
compressor runs 10 min. or more total.
• 15
th
retry: STD1 compressor stops due to error
—
—
1
[F3 retry code]
10
(F3 output)
—
14
—
ON if AIRNET not present
STD1 compressor stops due to error
19
STD2
discharge
pipe
temperature
retry
F3
Discharge
pipe
thermistor
(for STD2)
Td3 was 150°C or higher
—
—
—
ON if AIRNET not present
1
12
STD2 compressor error is confirmed
(confirmed on 1
st
occurrence)
9
• Td3
≤
100°C & standby time: 3 - 10 min.
• 10
th
retry: "F3" is output to AIRNET
• During retries, target Td3 limitation exists
• Retry counter decrements 1 when STD2
compressor runs 10 min. or more total.
• 15
th
retry: STD2 compressor stops due to error
—
—
1
[F3 retry code]
10
(F3 output)
—
14
—
ON if AIRNET not present
STD2 compressor stops due to error
20
Wet
operation
from
refrigeration
suction pipe
F4
Suction
thermistor
Discharge
thermistor
High pressure
sensor
Low pressure
sensor
These conditions continued for 10 minutes.
Suction SH < 5 K
Discharge SH < 5 K
—
—
ON if compressor on refrigeration
equipment is running.
—
ON if AIRNET not present
1
00
—
Reset the remote controller or the operation
switch, or recycle power
In addition to F4 warning condition,
discharge SH < 5 K for 6 hours.
—
—
OFF
—
—
00
System stop
21
Wet
operation
from Injection
pipe
F5
Thermistor
(Plate type
heat
exchanger
outlet)
Discharge
thermistor
High pressure
sensor
Low pressure
sensor
Suction
thermistor
These conditions continued for 10 minutes.
Suction SH > 5 K
Discharge SH < 10 K
—
—
ON if compressor on refrigeration
equipment is running.
—
ON if AIRNET not present
1
00
—
Reset the remote controller or the operation
switch, or recycle power
In addition to F5 warning condition,
discharge SH < 10 K for 6 hours.
—
—
OFF
ON
—
00
System stop
22
3 sensors
abnormal
H0
Each
temperature
thermistor and
pressure
sensor
Each temperature thermistor and pressure
sensor
—
—
OFF
ON
OFF
1
00
Any 3 of the following sensors: high
pressure sensor, intermediate pressure
sensor, low pressure sensor (for
refrigeration, air conditioning), each
discharge pipe thermistor, suction pipe
thermistor, (for refrigeration, air
conditioning), heat exchanger outlet
thermistor, outdoor air thermistor, heat
exchanger thermistor
Recycle power, or reset the operation
switch.
23
HPS1, HPS2
fault
detection
H3
HPS1, 2
—
—
OFF
ON
OFF
1
00
INV. compressor and STD1 compressor
stop
Recycle power, or reset the operation
switch.
24
HPS3 fault
detection
H3
HPS3
—
—
ON if compressor on refrigeration
equipment is running.
—
ON if AIRNET not present
1
00
STD2 compressor stops
List of Error Codes (LRYEQ16AY1)
No.
Item
Code
(Remote
controller
display)
Detection
device
Detection conditions
Times of retry
Retry action
R1 signal
Abnormal
stop output
Output during backup
(Only when AIRNET
address is 0)
Times when using
AIRNET output
Sub-classification code
(only for BRC1E1/2/3
remote controllers)
Processing after error is confirmed
Reset procedure
&
These conditions continued for a total
of 10 min.
• When any of the compressors are
Td > 110˚C & opening degree of
Y3E or Y4E or Y5E is 450 pls or
more
• Opening degree of Y2E is 450 pls
or more
OR
• Td1 > 120˚C continues 70 sec. or
more
• Td1 > 125˚C continues 30 sec. or
more
• Td1 > 130˚C
OR
• Td2 > 120˚C continues 70 sec. or
more
• Td2 > 125˚C continues 30 sec. or
more
• Td2 > 130˚C
OR
• Td3 > 120˚C continued 70 sec. or
more
• Td3 > 125˚C continued 30 sec. or
more
• Td3 > 130˚C
&
• Compressor guard timer timed up
• HPS1, HPS2 is activated (HPS1,
HPS2 contacts are open)
• DC compressor is stopped
• STD1 compressor is stopped
• Operation switch is ON
These conditions continued 2 min.
&
• HPS3 is activated (HPS3 contacts
are open)
• STD2 compressor is stopped
• Operation switch is ON
• NON2 compressor guard timer
timed up
• NON2 compressor is normal
• Air conditioning thermostat ON
conditions are met
These conditions continued 2 min.