SiBE811001EB
Troubleshooting
CONVENI-PACK
160
(1) Monitor mode
No.
Setting Item
LED Display
Data
Display
H1P H2P H3P H4P H5P H6P H7P
0
Abnormality (latest)
l h h h h h h
See next
page
1
INV. system
k h h h h h k
Data
2
Electronic expansion valve
k h h h h k h
Data
3
Pressure sensor
k h h h h k k
Data
4
Thermistor (1)
k h h h k h h
Data
5
Thermistor (2)
k h h h k h k
Data
7
Protection device
k h h h k k k
Data
8
Transmission system
k h h k h h h
Data
9
Abnormality of the inverter system (1)
k h h k h h k
Data
10 Abnormality of the inverter system (2)
k h h k h k h
Data
14 Abnormality (latest)
k h h k k k h
See next
page
15 Abnormality (last but 1)
k h h k k k k
16 Abnormality (last but 2)
k h k h h h h
20 Retry (latest)
k h k h k h h
21 Retry (last but 1)
k h k h k h k
22 Retry (last but 2)
k h k h k k h
The numbers in the "No." column represent the number of times to press the
button.
Press the SET (BS2) button and set the
LED display to a setting item.
Press the MODE (BS1) button in "Setting
mode 1" and set to "Monitor mode."
<Selection of setting item>
<Confirmation on setting contents>
Press the RETURN (BS3) button and
switches to the initial status of the
"Monitor mode."
∗
Press the MODE (BS1) button and
returns to "Setting mode 1."
Press the RETURN (BS3) button to
display different data of set items.
SET (BS2)
<Date
-
>
Data
k h h h h k h
Detect the earth leakage in the
inverter system
Data
k h h h h h k
Defective the electronic expansion
valve (Y1E)
k h h h h k h
Defective the electronic expansion
valve (Y2E)
Data
k h h h h h k
Defective the low pressure sensor
(S1NPL1)
Data
k h h h h h k
Defection the discharge pipe
thermistor of INV. compressor (R31T)
Data
k h h h h h k
Defection the heat exchanger inlet
thermistor (R3T)
k h h h h k h
Defection the heat exchanger outlet
thermistor (R6T)
Data
k h h h h h k
Defection the high pressure switch
Data
k h h h h h k
Defection the inverter transmission
system
k h h h h k h
Displayed while transmitting with the
outdoor unit after start-up
Data
k h h h h h k
Error "L1" occurs
k h h h h k h
Error "L4" occurs
k h h h k h h
Error "L5" occurs
k h h k h h h
Error "L8" occurs
k h k h h h h
Error "L9" occurs
Data
k h h h h h k
Error "E5" occurs
k h h h h k h
Error "U2" occurs
k h h h k h h
Error "P1" occurs
k h h k h h h
Error "P4" occurs