Troubleshooting
SiBE811001EB
163
CONVENI-PACK
8.4.2 PCB Abnormality
Error Code
A1
Applicable
Models
All indoor models
Method of Error
Detection
Check data from E²PROM.
Error Decision
Conditions
When data could not be correctly received from the E²PROM
E²PROM: Type of nonvolatile memory. Maintains memory contents even when the power
supply is turned OFF.
Supposed
Causes
External factor (Noise etc.)
Defective indoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Turn power supply OFF, then power
ON again.
The indoor unit PCB is normal.
External factor other than error
(for example, noise etc.).
Replace the indoor unit PCB.
Does the
system return
to normal?
YES
NO