Summary of Contents for INTEVIO RK-ZONE8

Page 1: ...M_2000060504_EN_1 0 INTEVIO Zone Expander Product Instructions Model RK ZONE8 M_2000061160_UL_1 1 ...

Page 2: ......

Page 3: ...r to extend power supply line Do not block the equipment s ventilation opening or put other equipment on it Safety guideline Protect this equipment against rainwater or moisture so as to avoid fire or electric shock Unpacking After removing the amplifier from the carton inspect for any exterior damage to the unit If damage is noted notify the carrier at once so that a claim can be justified Save a...

Page 4: ...ar water Clean only with a dry cloth Do not block any ventilation openings Install in accordance with the manufacturer s instructions Do not install on or near any heat sources such as radiators heat registers stoves or other apparatus including amplifiers that produce heat Do not defeat the safety purpose of the polarized or grounding type plug A polarized plug has two blades with one wider than ...

Page 5: ...ses shall be placed on the apparatus WARNING To reduce the risk of fire or electric shock do not expose this apparatus to rain or moisture The mains plug is used as disconnecting device and shall remain readily operable The apparatus is unsuitable for use in air handling spaces This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may...

Page 6: ...4 Password Precaution Please change the password during the system deployment Users need to change the password regularly The password with six numbers is preferred ...

Page 7: ...ontact outputs 4 external power amplifiers and 1 spare power amplifier can be connected Flexible amplifier redundancy function Full supervision including main power supply backup power supply CPU fault power amplifier speaker lines dry contact inputs network fault etc Speaker line supervision in non broadcasting state The volume of the signal to amplifiers can be set via RK MCU Supports 3 wire and...

Page 8: ...uts Front Panel No Button Indicator Light Description 1 Device status indicators Indicators for power supply main power fault backup power fault earth fault CPU fault network fault open circuit and short circuit of dry contact inputs 2 Power amplifier indicators Power amplifier loop fault indicators 3 Speaker lines indicators 8 zone status indicators ...

Page 9: ...nal audio devices such as CD DVD player tuner etc 4 Contact outputs 8 dry contact output interfaces used to control external devices 5 Contact inputs 8 dry contact input interfaces which can be connected to third party devices and used for business purpose Debug interface is used to upgrade the firmware 6 Power amplifier interface Amplifier interface for connection to the external power amplifiers...

Page 10: ...to RK MCU or zone expanders 12 Loudspeaker interface Speaker line interfaces of 8 zones each zone has two separate speaker lines A B 13 External amplifier interface The 70V audio interface of external power amplifiers including CH1A IN CH1B IN CH2A IN CH2B IN 14 Spare amplifier interface The 70V audio interface of spare amplifiers 15 DC output DC24V power output 16 Main power fuse AC power supply ...

Page 11: ...nput impedance 10 KΩ Frequency response 80Hz 18KHz 3dB SNR 80dB A weighted Audio Output Output channels CH1 CH2 Output signal 1V 0dBV THD 0 1 Power Amplifier Interface Number 3 CH1 CH2 and spare amplifier Output signal 1 4V THD 0 1 Control signal Self testing amplifier fault and energy saving signal Loudspeaker Interface Zone number 8 each zone has 2 speaker line A and B Max load power 500W ...

Page 12: ...ts AC 250V DC 30V Maximum current of the outputs 2 5A Others DC Power output 24V 1A Working Conditions Relative humidity 95 without condensing Operating temperature 10 C 55 C 14 F to 131 F Storage temperature 40 C 70 C 40 F to 158 F Specification Dimension W H D 18 98 3 46 16 02 inches Packing dimension W H D 22 85 9 25 21 73 inches Net weight 16 53 lbs Gross weight 22 71 lbs ...

Page 13: ...tact output terminal 3 5 6P 4 4 Loudspeaker terminal 5 08 16P 2 5 Power amplifier terminal 5 08 2P 6 6 DC Power output terminal 5 08 2P 1 7 Backup power terminal 7 62 4P 1 8 Twisted pair cable 2m 1 9 Audio cable 1 10 AC power supply cable 1 11 Fuse 2A 1 12 Product instructions 1 13 Machine Legs 4 ...