InteliDrive DCU Industrial 3.4.0 Global Guide
322
For 10 V input voltage range connects external resistors R1, R2
and select sensor characteristic 10 V
R1=10 kΩ, R2=2.7 kΩ.
D terminal is shielding
Note:
If the thermocouples are connected to IS-AIN8, appropriate jumpers must be removed (see rear sticker).
(jumpers are placed under the cover)