InteliDrive DCU Industrial 3.4.0 Global Guide
73
Binary
List contains 128 internal binary values (bits)
PLC Bout 1.1 to PLC BOUT 16.8
that
can be configured as any PLC function binary input or output.
Only used
PLC Bout x.x
can be configured to ID-DCU Industrial controller or external
modules physical terminals.
Used values are visible at controller screen.
Analog
There are available 96 internal analog values
PLC Aout 1
to
PLC Aout 96
that can be
configured as any PLC function input or output.
Any used
PLC Aout x
can be configured as physical analog output.Used values are
visible at controller screen.
PLC resource
Unsigned value that is automatically used for
Counter
and
Timer
functions, 16 PLC
resources are available.
Values are visible in InteliMonitor only.
PLC values
5.2.2 List of available PLC functions
Note:
Exact description of all available PLC functions can be found in DriveConfig-3.3 User Guide or in
DriveConfig context help (F1 key when a PLC function is selected).
IMPORTANT: Logic for controlling the motor can't be locked in PLC. Certification authority can ask
for access to the content locked this way.
PLC Function
Selection Available
Number of available blocks in ID-DCU Industrial 3.4.0
OR/AND
128x
XOR/RS
128x
Comp Hyst
24x
Comp Time
16x
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...