Relays inputs (galvanic separated)
Voltage level is defined between binary input and binary input COM terminal
Number of inputs
8 + 8
Input resistance
3000 Ω
Input voltage range
0-36 VDC
Input voltage level for open contact
8 to Power supply VDC
Input voltage level for close contact
0 to 2 VDC
Frequency inputs* (for IS-CU only)
RPM1
Type of sensor
Magnetic pick-up
Minimum input voltage
2 Vpk-pk (from 4 Hz to 4 kHz)
Maximum input voltage
50 Veff
Maximum measured frequency
8 kHz (min. input voltage 6Vpk-pk), frequency mode
RPM2
Type of sensor
Contact or Active sensor
Minimal pulse width
10 ms, integration mode
Maximum measured frequency
60 Hz, integration mode
Relays outputs
(galvanic separated) only HW 3.0 (non galvanic separated) HW 2.1
Number of output
8
Maximum current
0.5A DC
Maximum switching voltage
36 VDC
Power supply
8 to 36 V DC
Protection front panel
IP20
Current consumption
250 mA** at 24 V
Humidity
95% without condensation
Storage temperature
- 40 °C to + 80 °C
Operating temperature
- 30 °C to + 70 °C
Heat radiation
2 W
Standard conformity
Number of output
8
Low Voltage Directive
EN 61010-1:95 +A1:97
Electromagnetic Compatibility
EN 50081-1:94, EN 50081-2:96
EN 50082-1:99, EN 50082-2:97
*RPM1, RPM2 are available in IS-CU only
**During powering up current can be up to 1.5A
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...