178
Related FW
3.4.0
Related applications
AS, SS
Comm object
164
Description
is decreased / increased when the binary input is closed. Speed Down has
higher priority when both Up and Down inputs are active. RPM inc/dec rate is defined by
Engine speed can be set by
or by
and
Following Speed Request initialization is valid when
is not configured.
Speed Request (Idle) = 0.0 %. Inputs are active in LOC (Local) mode.
Speed Request (Running) = 50.0 % for AUX (ECU 50 % = Nominal RPM).
Speed Request (Running) = 0.0 % for PRP.
See Engine Values:
and
modes.
The Binary inputs SpeedUp and SpeedDown ramp
function is for the 0.6 sec constant 0.4 %/s and does not
depend on
setting. This
function enables fine setting of Engine speed to specific
like 1500 RPM value.
Dual rate ramp
Note:
Minimal Speed Up and Speed Down pulse duration is 110 ms to be accepted by controller.
Speed Down