InteliDrive DCU Industrial 3.4.0 Global Guide
180
Related FW
3.4.0
Related applications
AS, SS
Comm object
167
Description
This input changes state of logical binary output
Droop Sw
that can be configured as J1939 output to
change ECU mode. Input is active only when
Basic setting
: Governor Mode = BIN.INPUT (DROOP when
closed).
BI Droop
Related FW
3.4.0
Related applications
AS, SS
Comm object
168
Description
This input changes state of
that can be configured as J1939 output
to change ECU mode. Input is active only when
t = BIN.INPUT.
BI Second RPM
Related FW
3.4.0
Related applications
AS, SS
Comm object
169
Description
This input changes state of
that can be configured as J1939 output to change
ECU mode. Input is active only when
= BIN.INPUT.
BI Idle
Related FW
3.4.0
Related applications
AS, SS
Comm object
172
Description
Rem Start/Stop is level signal that activates engine start when closed and stop after is opened. It is inactive
in LOC (Local) mode.
It is not possible to stop engine by panel Stop button and by
when Rem Start/Stop
is active. Rem Start/Stop input can be configured to Binary output Timer active to enable engine automatic
start/stop function – see
.
Note:
Engine “Start fail” is Warning (level 1) protection and does not block another start when Rem
Start/Stop is still closed. To prevent unlimited number of starts – configure on
Sd protection.
Note:
Engine stays running when Rem Start/Stop is opened in controller LOC (Local) mode.
Rem Start/Stop
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...