InteliDrive DCU Industrial 3.4.0 Global Guide
343
BOOT
Programming
RESET
Programming / reset
Tx, Rx
CAN 1data
ST
Power/module state
Address and jumpers setting
CAN Address
The module CAN address is set by jumpers A1 and A2. Set module CAN address correspondingly to
configuration according table below.
CAN Address
A1
A2
1
Open
Open
2
Close
Open
3
Open
Close
4
Close
Close
Table 8.13 Setting CAN address
Output mode
Follow the p – I – I – U symbols on the module sticker. There are two equivalent positions for current output.
AOUT
Symbol
Function
p
PWM
Pulse-Width-Modulation
l
0 to 20 mA DC
U
0 to 10 V DC
Table 8.14 Setting output mode
Programming firmware
Firmware upgrade is via AT-link (TTL). For programming it is necessary to close jumper BOOT. RESET jumper
is used to reset the device. Close jumper to reset the device. For programming is used FlashProg PC tool.
CAN1 termination
I-AOUT8 has own CAN terminating resistor (120 ohm). Close jumper CAN-R to connect terminating resistor to
CAN bus, open jumper CAN-R disconnecting terminating resistor.
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...