InteliDrive DCU Industrial 3.4.0 Global Guide
194
Related FW
3.4.0
Related applications
AS, SS
Comm object
256
Description
The output closes if any Wrn, Sd, Cd, Fls, alarm is active and stays closed until all alarms disappear and
Fault reset is pressed = output is opened when Alarm list is empty.
Common Alarm
Related FW
3.4.0
Related applications
AS, SS
Comm object
3
Description
The output closes when any Warning alarm is active. Output opens when all Wrn alarms disappear and Fault
reset is pressed (no Wrn alarm in Alarm list).
Common Wrn
Related FW
3.4.0
Related applications
AS, SS
Comm object
4
Description
The output closes when any Shut-down alarm is active. Output opens when all Sd alarms disappear and
Fault reset is pressed (no Sd alarm in Alarm list).
Common Sd
Related FW
3.4.0
Related applications
AS, SS
Comm object
257
Description
The output closes when any Cool-down alarm is active. Output opens when all Cd alarms disappear and
Fault reset is pressed (no Cd alarm in Alarm list).
Common Cd
Related FW
3.4.0
Related applications
AS, SS
Comm object
6
Description
The output closes when any Sensor fail alarm is active. Output opens when all Fls alarms disappear and
Fault reset is pressed (no Fls alarm in Alarm list).
Common Fls
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...