InteliDrive DCU Industrial 3.4.0 Global Guide
262
Related FW
3.4.0
Related applications
AS
Comm object
10000
Description
Output Value of Loadsharing functional block inside ID-DCU Industrial controller. It is
influenced by loadsharing variation signal (this signal can increase / decrease the RQSP Ramp value
by ±1.5 %). The ThrottlePos value is intended to send as required speed to an engine. Load sharing block
diagram.
See following chart describing ThrottlePos value in Running and Loadsharing state.
Note:
The regulation speed of loadsharing variation signal (max 1.5 %) is given by PI loop parameters
and
. The Loadsharing: ThrottlePos value is influenced by
ramping specified by Loadsharing: RQSP Ramp setpoint.
Note:
The Loadsharing state can be activated from Running state and if both following conditions are
met:
Actual Engine speed is in range specified by setpoints
and
is active (or I/0 front panel button is pressed)
There is loadsharing activation delay specified by setpoint Loadsharing: Clutch Del to postpone
loadsharing regulation after transient events after engine mechanical connection to gear-box.
Note:
It is essential requirement to configure engine load information (ECU value “actual load”, physical
analog input reading actuator position feedback or boost pressure etc.) into
for loadsharing functionality.
Note:
All ID-DCU Industrial controllers working in the same loadsharing group have to be interconnected
on CAN2 bus, controllers must have different controller addresses.
Note:
Loadsharing state - the Loadsharing: Back Up Speed value is taken into account instead of
if the
indicates Sensor Fail (#####) and
is active.
ThrottlePos
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...